Publicación: Experimental assessment of different mixing air ventilation systems on ventilation performance and exposure to exhaled contaminants in hospital rooms
Cargando...
Fecha
2018-08-23
Editor/a
Director/a
Tutor/a
Coordinador/a
Prologuista
Revisor/a
Ilustrador/a
Derechos de acceso
info:eu-repo/semantics/openAccess
Título de la revista
ISSN de la revista
Título del volumen
Editor
Elsevier
Resumen
This study evaluates the convenience of the use of four different mixing ventilation configurations in individual hospital rooms (IHR) based on ventilation performance and health workers (HW) exposure to the contaminants released by a confined patient (CP). Two supply configurations: grilles in the upper part of a wall (G) and swirl ceiling diffusers (S), combined with two different exhaust grilles positions in the opposite wall: upper part (U) and lower part (D) are tested using typical IHR set up. Occupants are represented by thermal breathing manikins, CP lies on a bed while HW stands close to it. Three air renewal rates are tested to determine their influence in the studied variables, 6, 9 and 12 ACH covering the whole range of ventilation requirements of such spaces. The experimental conditions considering the thermal comfort of the occupants are taken into account. Different ventilation configurations create different air distribution patterns inside the room. G configurations lead to high HW transient exposure values while S maintain low values that decrease when ACH is increased, so this second configuration is preferred for IHRs. Results are also compared with a displacement ventilation (DV) study highlighting the convenience of this strategy for IHRs.
Descripción
The registered version of this article, first published in Energy and Buildings, is available online at the publisher's website: Elsevier, https://doi.org/10.1016/j.enbuild.2018.07.053
La versión registrada de este artículo, publicado por primera vez en Energy and Buildings, está disponible en línea en el sitio web del editor: Elsevier, https://doi.org/10.1016/j.enbuild.2018.07.053
La versión registrada de este artículo, publicado por primera vez en Energy and Buildings, está disponible en línea en el sitio web del editor: Elsevier, https://doi.org/10.1016/j.enbuild.2018.07.053
Categorías UNESCO
Palabras clave
mixing ventilation, hospital room, personal exposure, ventilation effectiveness thermal comfort, airborne transmission of diseases
Citación
Berlanga, F. A., Olmedo, I., Adana, M. R. D., Villafruela, J. M., José, J. F. S., & Castro, F. (2018). Experimental assessment of different mixing air ventilation systems on ventilation performance and exposure to exhaled contaminants in hospital rooms. Energy and Buildings, 177, 207-219. https://doi.org/10.1016/j.enbuild.2018.07.053