Experimental variation of the personal exposure in a hospital room influenced by wall heat gains

Fecha
2019-03-25
Autores
Olmedo, Inés
Villafruela, José Manuel
Ruiz de Adana, M.
Editor/a
Director/a
Tutor/a
Coordinador/a
Prologuista
Revisor/a
Ilustrador/a
Derechos de acceso
info:eu-repo/semantics/openAccess
Título de la revista
ISSN de la revista
Título del volumen
Editor
Elsevier
Proyectos de investigación
Unidades organizativas
Número de la revista
Resumen
Homogenous indoor temperature of the walls in hospital rooms may be a difficult condition to be reached. Solar radiation increases heat loads in building walls, especially glazed walls, increasing their superficial temperature. This paper aims to investigate the influence of a wall heat gain, simulated experimentally by a radiant wall (RW), on the distribution of indoor exhaled contaminants and therefore the exposure to a person. An experimental setup of a single hospital room is considered with a patient in repose (PR) being the source of exhaled contaminants, and a health worker (HW) standing and being the exposed person. Four different positions of HW relative to PR and RW are studied. The experiments are carried out using 6 and 12 air changes per hour (ACH) and with active and inactive RW, simulating sunny and shaded conditions of an external wall. The concentration of exhaled contaminants is measured in the microenvironment and the inhalation of HW. The exposure of HW to the exhaled contaminants is compared for a total of 16 experiments. Results show that wall heat gains significantly change the distribution of exhaled contaminants. RW active generates “clean” and “polluted” areas of exhaled contaminants at both sides of the bed that changes when using 6 or 12 ACH. Moreover, with RW active, the use of 12 ACH not always leads to a decrease of HW exposure. The intake fraction, IF, is a more suitable index than the personal exposure, einh, since illustrates the dilution of inhaled contaminants respect to the source.
Descripción
The registered version of this article, first published in Building and Environment, is available online at the publisher's website: Elsevier, https://doi.org/10.1016/j.buildenv.2019.03.008
La versión registrada de este artículo, publicado por primera vez en Building and Environment, está disponible en línea en el sitio web del editor: Elsevier, https://doi.org/10.1016/j.buildenv.2019.03.008
Categorías UNESCO
Palabras clave
internal wall surface temperature, wall heat gains, intake fraction, exposure to exhaled contaminants, mixing ventilation