Publicación: Exhaled contaminant concentration data in a hospital room influenced by external heat gains
Cargando...
Fecha
2019-05-18
Editor/a
Director/a
Tutor/a
Coordinador/a
Prologuista
Revisor/a
Ilustrador/a
Derechos de acceso
info:eu-repo/semantics/openAccess
Título de la revista
ISSN de la revista
Título del volumen
Editor
Elsevier
Resumen
A hospital room is simulated using two breathing thermal manikins representing a health worker (HW) and a patient in repose (PR). The PR exhales R134a simulating small exhaled particles (<5 μm) and the contaminant concentration around and in the inhalation of HW is measured during a period of 2 hours per experiment. The room is climatized to maintain constant air temperature values of 25 °C using two wall mounted grilles and two exhausts. The air change per hour (ACH) used varies from 6 to 12 in order to evaluate its influence on the dispersion of exhaled contaminants. An external heat gain is simulated by a radiant wall (RW) that is active or inactive during the experiments. When RW is active the external heat gain simulated is 39.7 W/m2, which corresponds to a solar external radiation typical in many countries worldwide. The contaminant concentration is measured at different locations around HW and in the inhalation tube. The temperature gradient in the room is also measured along a vertical pole. The discussion of the results of the 16 experimental cases can be found in Ref. [1].
Descripción
The registered version of this article, first published in Data in Brief, is available online at the publisher's website: Elsevier, https://doi.org/10.1016/j.dib.2019.103978
La versión registrada de este artículo, publicado por primera vez en Data in Brief, está disponible en línea en el sitio web del editor: Elsevier, https://doi.org/10.1016/j.dib.2019.103978
La versión registrada de este artículo, publicado por primera vez en Data in Brief, está disponible en línea en el sitio web del editor: Elsevier, https://doi.org/10.1016/j.dib.2019.103978
Categorías UNESCO
Palabras clave
Intake fraction, Exhaled contaminants distribution, External heat gains
Citación
Olmedo, I., Berlanga, F. A., Villafruela, J. M., & Ruiz de Adana, M. (2019a). Exhaled contaminant concentration data in a hospital room influenced by external heat gains. Data in Brief, 24, 103978. https://doi.org/10.1016/j.dib.2019.103978